Siemens SINAMICS G120 - p9366 SI Motion SDI stop response (processor 2); SI Mtn SDI Stop P2; p9368 SI Motion SAM velocity limit (processor 2); SI Mtn SAM v_limP2; p9370 SI Motion acceptance test mode (processor 2); SI Mtn acc_mod P2; r9371 SI Motion acceptance test status (processor 2); SI Mtn acc_stat P2

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
397
2 Parameters
2.2 List of parameters
Description: Sets the stop response for the function "Safe motion direction" (SDI).
This setting applies to both directions of motion.
In the case of encoderless motion monitoring (p9306 = 1), only a value of 0 or 1 is permitted.
Value: 0: STOP A
1: STOP B
Dependency: Refer to: p9364, p9365
Refer to: C30716
Note: SDI: Safe Direction (safe motion direction)
Description: Sets the velocity tolerance limit for the "SAM" function.
SAM is de-activated once the set velocity limit has been undershot.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description: Setting to select and de-select the acceptance test mode.
Value: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9358, r9371
Refer to: C01799
Note: Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives, are
enabled (p9601.2/p9801.2).
Description: Displays the status of the acceptance test mode.
p9366 SI Motion SDI stop response (processor 2) / SI Mtn SDI Stop P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2824
Min Max Factory setting
0 1 1
p9368 SI Motion SAM velocity limit (processor 2) / SI Mtn SAM v_limP2
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [rpm] 1000.00 [rpm] 0.00 [rpm]
p9370 SI Motion acceptance test mode (processor 2) / SI Mtn acc_mod P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00AC hex 0000 hex
r9371 SI Motion acceptance test status (processor 2) / SI Mtn acc_stat P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0000 hex 00AC hex -