SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
267
2 Parameters
2.2 List of parameters
For bit 13 = 1:
After the measurement has been completed, the system immediately goes into closed-loop speed controlled
operation.
Dependency: Refer to: F07988
Note: The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
Description: Sets the configuration of the rotating measurement.
Dependency: Refer to: F07988
Note: The following parameters are influenced for the individual optimization steps:
Bit 01: p0320, p0360, p0362 ... p0369
Bit 02: p0341, p0342
Bit 03: p1400.0, p1458, p1459, p1463, p1470, p1472, p1496
Bit 04: Dependent on p1960
p1960 = 1, 3: p1400.0, p1458, p1459, p1470, p1472, p1496
Description: Sets the rotating measurement.
The rotating measurement is carried out after the next switch-on command.
The setting possibilities of the parameter depend on the open-loop/closed-loop control mode (p1300).
p1300 < 20 (U/f open-loop control):
It is not possible to select rotating measurement or speed controller optimization.
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller
parameters
Yes No -
04 Speed controller optimization (vibration test) Yes No -
11 Do not change the controller parameters
during the measurement
Yes No -
12 Measurement shortened Yes No -
13 After measurement direct transition into
operation
Yes No -
p1959[0...n] Rotating measurement configuration / Rot meas config
PM250
PM260
Access level: 3 Calculated: p0340 = 1 Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 0000 0001 1110 bin
Bit field: Bit Signal name 1 signal 0 signal FP
01 Saturation characteristic identification Yes No -
02 Moment of inertia identification Yes No -
03 Re-calculates the speed controller
parameters
Yes No -
04 Speed controller optimization (vibration test) Yes No -
11 Do not change the controller parameters
during the measurement
Yes No -
p1960 Rotating measurement selection / Rot meas sel
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 3 0