SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
41
2 Parameters
2.2 List of parameters
Notice: p2081 is used to define the signal sources of the PROFIdrive status word interconnection.
Note: The following status bits are displayed in r0053:
Bit 00: r1239 Bit 8
Bit 01: r2197 Bit 5 (negated)
Bit 02: r2197 Bit 0 (negated)
Bit 03: r2197 Bit 8
Bit 04: r2197 Bit 2
Bit 05: r2197 Bit 1
Bit 06: r2197 Bit 4
Bit 07: r2197 Bit 9
Bit 08: r2197 Bit 10
Bit 09: r1199 Bit 2 (negated)
Bit 10: r2349 Bit 10
Bit 11: r2349 Bit 11
Description: Displays control word 1.
Note: The following control bits are displayed in r0054:
Bit 00: r0898 Bit 0
Bit 01: r0898 Bit 1
Bit 02: r0898 Bit 2
Bit 03: r0898 Bit 3
Bit 04: r0898 Bit 4
Bit 05: r0898 Bit 5
Bit 06: r0898 Bit 6
02 |n_act| > p1080 (n_min) Yes No -
03 I_act >= p2170 Yes No -
04 |n_act| > p2155 Yes No -
05 |n_act| <= p2155 Yes No -
06 |n_act| >= r1119 (n_set) Yes No -
07 Vdc <= p2172 Yes No -
08 Vdc > p2172 Yes No -
09 Ramp-up/ramp-down completed Yes No -
10 Technology controller output at the lower
limit
Yes No -
11 Technology controller output at the upper
limit
Yes No -
r0054.0...15 CO/BO: Control word 1 / STW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 No Yes -
02 OC / OFF3 No Yes -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -
05 Continue ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master control by PLC Yes No -
11 Direction reversal (setpoint) Yes No -
13 Motorized potentiometer raise Yes No -
14 Motorized potentiometer lower Yes No -
15 CDS bit 0 Yes No -

Table of Contents