EasyManua.ls Logo

Siemens SINAMICS G120 - p1130[0...n] Ramp-function generator initial rounding-off time; RFG t_start_round; p1131[0...n] Ramp-function generator final rounding-off time; RFG t_end_delay; p1134[0...n] Ramp-function generator rounding-off type; RFG round­off type

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
169
2 Parameters
2.2 List of parameters
Note: For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
If the maximum speed p1082 changes, p1127 is re-calculated.
If a braking resistor is connected to the DC link (p0219 > 0), then the minimum ramp-down time is automatically
adapted using p1127.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator.
The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function
generator.
Value: 0: Cont smoothing
1: Discont smoothing
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM230
PM230_STO
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
PM230
PM230_STO
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 2.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
PM240
PM250, PM260
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1134[0...n] Ramp-function generator rounding-off type / RFG round-off type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 3070
Min Max Factory setting
0 1 0