EasyManua.ls Logo

Siemens SINAMICS G120 - p2265 Technology controller actual value filter time constant; Tec_ctrl act T; r2266 CO: Technology controller actual value after filter; Tec_ctr act aftFlt; p2267 Technology controller upper limit actual value; Tec_ctrl u_lim act; p2268 Technology controller lower limit actual value; Tec_ctrl l_lim act

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
333
2 Parameters
2.2 List of parameters
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
Description: Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Refer to: F07426
Notice: If the actual value exceeds this upper limit, this results in fault F07426.
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: Refer to: p2264, p2265, p2271
Refer to: F07426
Notice: If the actual value falls below this lower limit, this results in fault F07426.
Description: Sets the scaling factor for the actual value of the technology controller.
Dependency: Refer to: p2264, p2265, p2267, p2268, p2271
Note: For 100%, the actual value is not changed.
p2265 Technology controller actual value filter time constant / Tec_ctrl act T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
- [%] - [%] - [%]
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: -
Unit group: 9_1 Unit selection: p0595 Func. diagram: 7958
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2269 Technology controller gain actual value / Tech_ctrl gain act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [%] 500.00 [%] 100.00 [%]