SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
593
3 Function diagrams
3.5 Communication PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
Fig. 3-28 2450 – PROFIdrive - PZD send signals interconnection
- 2450 -
Function diagram
87654321
fp_2450_97_64.vsd
PROFIdrive (PROFIBUS/PROFINET), EtherNet/IP
CU240B/E-2_DP/PN
09.12.2015 V4.7.6
PROFIdrive - PZD send signals interconnection
PZD send word 1...8
p2051[0...16] WORD
r2053[0...16] WORD
...
U16 -r2089[0]2 [2452]ZSW1
I16 4000 hex p2000r0063[0]6 -NIST_A
FAULT_CODE
U16
r2131301 [8060] U16
r2132303 [8065]WARN_CODE
U16r311358MELD_NAMUR -
4000 hex p2004I16r0082[1]54 [6799]PIST_GLATT
4000 hex p2003I16r0080[1]53 [6799]MIST_GLATT
4000 hex p2002I16r0068[1]51 [6799]IAIST_GLATT
4000 hex p2000I16r0063[1]57 -NIST_A_GLATT
PROFIBUS
PROFINET
Signal sources for PZD send signals
Signal
PROFIdrive
Signal No.
Interconnection
parameter
Function diagram Data type Scaling
Status word 1
Actual speed A (16 bit)
Absolute actual current, smoothed
Actual torque smoothed
Power factor, smoothed
Actual speed, smoothed
VIK-NAMUR message bit bar
Fault code
Alarm code
PROFIdrive send
telegram
Header
Data
Telegram
assignment
according to p0922
[2420]
Trailer
Data type according to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16.
Description
U16r0053305 [2456]ZSW3 Status word 3