SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
43
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the status word of the closed-loop control.
Description: Displays the actual speed setpoint at the input of the speed controller or U/f characteristic (after the interpolator).
Dependency: Refer to: r0020
Note: The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description: Display and connector output for the speed setpoint after the setpoint filters.
03 Soft starting present Yes No -
04 Magnetizing completed Yes No -
05 Voltage boost when starting Active Inactive 6301
06 Acceleration voltage Active Inactive 6301
07 Frequency negative Yes No -
08 Field weakening active Yes No -
09 Voltage limit active Yes No 6714
10 Slip limit active Yes No 6310
11 Frequency limit active Yes No -
12 Current limiting controller voltage output
active
Yes No -
13 Current/torque limiting Active Inactive 6060
14 Vdc_max controller active Yes No 6220,
6320
15 Vdc_min controller active Yes No 6220,
6320
r0056.0...13 CO/BO: Status word, closed-loop control / ZSW cl-loop ctrl
PM250
PM260
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2526
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Initialization completed Yes No -
01 De-magnetizing completed Yes No -
02 Pulse enable available Yes No -
03 Soft starting present Yes No -
04 Magnetizing completed Yes No -
05 Voltage boost when starting Active Inactive 6301
06 Acceleration voltage Active Inactive 6301
07 Frequency negative Yes No -
08 Field weakening active Yes No -
09 Voltage limit active Yes No 6714
10 Slip limit active Yes No 6310
11 Frequency limit active Yes No -
12 Current limiting controller voltage output
active
Yes No -
13 Current/torque limiting Active Inactive 6060
r0060 CO: Speed setpoint before the setpoint filter / n_set before filt.
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 2701, 6030, 6799
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
r0062 CO: Speed setpoint after the filter / n_set after filter
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 6020, 6030, 6031
Min Max Factory setting
- [rpm] - [rpm] - [rpm]