SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
197
2 Parameters
2.2 List of parameters
Description: Sets the proportional gain for the Vdc controller (DC link voltage controller).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note: The gain factor is proportional to the capacitance of the DC link.
The parameter is pre-set to a value that is optimally adapted to the capacitance of the power unit.
Description: Sets the integral time for the Vdc controller (DC link voltage controller).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Description: Sets the rate time constant for the Vdc controller (DC link voltage controller).
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Description: Sets the output limit for the Vdc min controller (DC link undervoltage controller).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1), "Dynamic Drive Control" (DDC, p0096
= 2)
Description: Activates/de-activates the automatic sensing of the switch-in level for the Vdc_max controller. When the sensing
function is de-activated, the activation threshold r1282 for the Vdc_max controller is determined from the
parameterized connection voltage p0210.
Value: 0: Automatic detection inhibited
1: Automatic detection enabled
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
p1290[0...n] Vdc controller proportional gain (U/f) / Vdc_ctrl Kp
PM230
PM230_STO
PM240
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0.00 100.00 1.00
p1291[0...n] Vdc controller integral time (U/f) / Vdc_ctrl Tn
PM230
PM230_STO
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 10000 [ms] 40 [ms]
p1292[0...n] Vdc controller rate time (U/f) / Vdc_ctrl t_rate
PM230
PM230_STO
PM240
Access level: 3 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0 [ms] 1000 [ms] 10 [ms]
p1293[0...n] Vdc min controller output limit (U/f) / Vdc_min outp_lim
PM240 Access level: 4 Calculated: p0340 = 1,3,4 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6320
Min Max Factory setting
0.00 [Hz] 600.00 [Hz] 600.00 [Hz]
p1294 Vdc_max controller automatic detection ON signal level (U/f) / Vdc_max SenseOnLev
PM230
PM230_STO
PM240
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0