2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
308 List Manual (LH11), 01/2016, A5E33839529
Description: Displays the system runtime in days when the alarm was cleared.
Dependency: Refer to: r2110, r2122, r2123, r2124, r2125, r2134, r2145
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Sets the signal source for the signal "ramp-function generator active" for the following signals/messages:
"Speed setpoint - actual value deviation within tolerance t_on" (BO: r2199.4)
"Ramp-up/ramp-down completed" (BO: r2199.5)
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The binector input is automatically interconnected to r1199.2 as a default setting.
Description: Sets the configuration for messages and monitoring functions.
Dependency: Refer to: r2197
Refer to: A07903
Note: For bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
For bit 01:
When the bit is set, the load monitoring is only executed in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
For bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
For bit 05:
When this bit is set, a change to open-loop speed controlled operation is only possible when the motor is stationary.
r2146[0...63] Alarm time removed in days / t_alarm res days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8065
Min Max Factory setting
- - -
p2148[0...n] BI: RFG active / RFG active
Access level: 3 Calculated: p0340 = 1,3,5 Data type: U32 / Binary
Can be changed: U, T Scaling: - Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 8011
Min Max Factory setting
- - 0
p2149[0...n] Monitoring configuration / Monit config
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 1001 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable alarm A07903 Yes No 8011
01 Load monitoring only in the 1st quadrant Yes No 8013
03 n_act > p2155 own hysteresis Yes No 8010
05 Stall monitoring for encoderless speed
control
Yes No -