2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
226 List Manual (LH11), 01/2016, A5E33839529
For closed-loop speed control, r1508 corresponds to the speed controller output; for closed-loop torque control,
r1508 corresponds to the torque setpoint of the signal source assigned in p1503.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the signal source for supplementary torque 1.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the signal source for scaling the supplementary torque 1.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the signal source for supplementary torque 2.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Sets the scaling for supplementary torque 2.
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Description: Displays the total supplementary torque.
The displayed value is the total of supplementary torque values 1 and 2 (p1511, p1512, p1513, p1514).
Dependency: Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
p1511[0...n] CI: Supplementary torque 1 / M_suppl 1
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 6020, 6060
Min Max Factory setting
- - 0
p1512[0...n] CI: Supplementary torque 1 scaling / M_suppl 1 scal
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 5060, 6060
Min Max Factory setting
- - 0
p1513[0...n] CI: Supplementary torque 2 / M_suppl 2
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: p2003 Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 6020, 6060
Min Max Factory setting
- - 0
p1514[0...n] Supplementary torque 2 scaling / M_suppl 2 scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: 6020, 6060
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
r1515 Supplementary torque total / M_suppl total
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2003 Dyn. index: -
Unit group: 7_1 Unit selection: p0505 Func. diagram: 6020, 6060
Min Max Factory setting
- [Nm] - [Nm] - [Nm]