SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
263
2 Parameters
2.2 List of parameters
Note: The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature
inductance Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit 19 = 1:
All parameters are automatically saved after a successful motor data identification.
If a speed controller optimization run is then selected, the parameters are only saved after this measurement has
been completed.
Bit 22 = 1:
Only that measurement is carried out that is required for the flying restart of a reluctance motor. The bit is reset after
a successful measurement
Description: Sets the motor data identification routine.
The motor data identification routine is carried out after the next switch-on command.
p1910 = 1:
All motor data and the drive converter characteristics are identified and then transferred to the following parameters:
p0350, p0354, p0356, p0357, p0358, p0360, p1825, p1828, p1829, p1830
After this, the control parameter p0340 = 3 is automatically calculated.
p1910 = 20:
Only for internal SIEMENS use.
Value: 0: Inhibited
1: Complete identification (ID) and acceptance of motor data
2: Complete identification (ID) of motor data without acceptance
20: Voltage vector input
21: Voltage vector input without filter
22: Rectangular voltage vector input without filter
23: Triangular voltage vector input without filter
24: Rectangular voltage vector input with filter
25: Triangular voltage vector input with filter
26: Enter voltage vector with DTC correction
27: Enter voltage vector with AVC
28: Enter voltage vector with DTC + AVC correction
Dependency: "Quick commissioning" must be carried out (p0010 = 1, p3900 > 0) before executing the motor data identification
routine!
When selecting the motor data identification routine, the drive data set changeover is suppressed.
Refer to: p1900
Refer to: F07990, A07991
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr
measurement
Yes No -
14 De-activate valve interlocking time
measurement
Yes No -
15 Determine only stator resistance, valve
voltage fault, dead time
Yes No -
16 Short motor identification (lower quality) Yes No -
17 Measurement without control parameter
calculation
Yes No -
18 After motID direct transition into operation Yes No -
19 After MotID automatically save results Yes No -
20 Estimate cable resistance Yes No -
p1910 Motor data identification selection / MotID selection
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 28 0