Siemens SINAMICS G120 - r0032 CO: Active power actual value smoothed; P_actv_act smth; r0033 Torque utilization smoothed; M_util smooth; r0034 CO: Motor utilization thermal; Mot_util therm

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
33
2 Parameters
2.2 List of parameters
Description: Displays the smoothed actual value of the active power.
Dependency: Refer to: r0082
Notice: This smoothed signal is not suitable for diagnostics or evaluation of dynamic operations. In this case, the
unsmoothed value should be used.
Note: Power delivered at the motor shaft.
The active power is available smoothed (r0032 with 100 ms) and unsmoothed (r0082).
Description: Displays the smoothed torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque in reference to the torque limit, scaled using
p2196.
Dependency: This parameter is only available for vector control. For U/f control r0033 = 0 %.
Note: Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
For M_set total (r0079) > 0, the following applies:
- Required torque = M_set total
- Actual torque limit = M_max upper effective (r1538)
For M_set total (r0079) <= 0, the following applies:
- Required torque = - M_set total
- Actual torque limit = - M_max lower effective (r1539)
For the actual torque limit = 0, the following applies: r0033 = 100 %
For the actual torque limit < 0, the following applies: r0033 = 0 %
Description: Display and connector output for the motor utilization from motor temperature model 1 (I2t) or 3.
For motor temperature model 1 (I2t) (p0612.0 = 1), the following applies:
For firmware version < 4.7 SP6 or p0612.12 = 0:
- r0034 = (motor model temperature - 40 K) / (p0605 - 40 K) * 100 %
From firmware version 4.7 SP6 and p0612.12 = 1:
- r0034 = (motor model temperature - p0613) / (p0605 - p0613) * 100 %
For motor temperature model 3 (p0612.2 = 1), the following applies:
- r0034 = (motor model temperature - p5397) / (p5398 - p5397) * 100 %
r0032 CO: Active power actual value smoothed / P_actv_act smth
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: r2004 Dyn. index: -
Unit group: 14_10 Unit selection: p0505 Func. diagram: 5730, 6799, 8750,
8850, 8950
Min Max Factory setting
- [kW] - [kW] - [kW]
r0033 Torque utilization smoothed / M_util smooth
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8012
Min Max Factory setting
- [%] - [%] - [%]
r0034 CO: Motor utilization thermal / Mot_util therm
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 8017