Siemens SINAMICS G120 - p1295[0...n] Vdc_min controller time threshold (U;f); Vdc_min t_thresh; p1296[0...n] Vdc_min controller response (kinetic buffering) (U;f; Vdc_min response; p1297[0...n] Vdc_min controller speed threshold (U;f); Vdc_min n_thresh; r1298 CO: Vdc controller output (U;f); Vdc_ctrl output

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G120 Control Units CU240B-2/CU240E-2
198 List Manual (LH11), 01/2016, A5E33839529
Description: Sets the time threshold for the Vdc_min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized.
Prerequisite: p1296 = 1
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Notice: If a time threshold has been parameterized, the Vdc_max controller should also be activated (p1280 = 3) so that the
drive does not shut down with overvoltage when Vdc_min control is exited (due to the time violation) and in the event
of fault response OFF3. It is also possible to increase the OFF3 ramp-down time p1135.
Description: Sets the response for the Vdc_min controller (kinetic buffering).
Value: 0: Buffer Vdc until undervoltage, n<p1297 -> F07405
1: Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note: For p1296 = 1:
The quick stop ramp entered in p1135 must not be equal to zero, to prevent overcurrent shutdown if F07406 is
triggered.
Description: Sets the speed threshold for the Vdc-min controller (kinetic buffering).
If this value is exceeded a fault is output; the required response can be parameterized .
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
Note: Exiting the Vdc_min control before reaching motor standstill prevents the regenerative braking current from
increasing significantly at low speeds, and after a pulse inhibit, means that the motor coasts down.
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
Dependency: Not visible with application class: "Dynamic Drive Control" (DDC, p0096 = 2)
p1295[0...n] Vdc_min controller time threshold (U/f) / Vdc_min t_thresh
PM240 Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.000 [s] 10000.000 [s] 0.000 [s]
p1296[0...n] Vdc_min controller response (kinetic buffering) (U/f / Vdc_min response
PM240 Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p1297[0...n] Vdc_min controller speed threshold (U/f) / Vdc_min n_thresh
PM240 Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Func. diagram: -
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 50.00 [rpm]
r1298 CO: Vdc controller output (U/f) / Vdc_ctrl output
PM230
PM230_STO
PM240
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dyn. index: -
Unit group: 3_1 Unit selection: p0505 Func. diagram: 6320
Min Max Factory setting
- [rpm] - [rpm] - [rpm]