4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120 Control Units CU240B-2/CU240E-2
870 List Manual (LH11), 01/2016, A5E33839529
Remedy: - check the device supply voltage (p0210).
- check the dimensioning of the line reactor.
See also: p0210 (Drive unit line supply voltage)
F30600 SI P2: STOP A initiated
Message class: Safety monitoring channel has identified an error (10)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive-integrated "Safety Integrated" function on processor 2 has detected an error and initiated a STOP A.
- forced checking procedure (test stop) of the safety switch-off signal path on processor 2 unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from processor 1.
1005:
- Pulses suppressed although STO not selected and there is no internal STOP A present.
- For a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B), these terminals are active
(DIP switch to "ON"). However, the "STO via terminals at the Power Module" function has not been enabled (p9601.7
= p9801.7 = 0).
1010: Pulses enabled although STO is selected or an internal STOP A is present.
1011: Internal fault for the pulse enable in the Power Module.
1030: Feedback signal of the safety switch-off signal paths for the "STO via terminals at the Power Module" function
different.
9999: Subsequent response to fault F30611.
Remedy: - select Safe Torque Off and de-select again.
- carry out a POWER ON (switch-off/switch-on) for all components.
- replace Power Module involved.
For fault value = 1005:
- de-activate terminals STO_A/STO_B on the Power Module (set both DIP-switches to "OFF") or enable the "STO via
terminals at the Power Module" function.
For fault value = 1030:
- check the discrepancy time, and if required, increase the value (p9650/p9850).
- check the STO terminal at the Power Module (contact problems).
For fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
PM: Power Module
STO: Safe Torque Off
F30611 (A) SI P2: Defect in a monitoring channel
Message class: Safety monitoring channel has identified an error (10)
Reaction: NONE (OFF1, OFF2, OFF3)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive-integrated "Safety Integrated" function on processor 2 has detected a fault in the crosswise data
comparison between the two monitoring channels and has initiated a STOP F.
As a consequence of this fault, fault F30600 (SI P2: STOP A initiated) is output.
Fault value (r0949, interpret decimal):
0: Stop request from the other monitoring channel.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9795.
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI F-DI changeover discrepancy time (p9650, p9850).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO (p9651, p9851).