EasyManuals Logo

Siemens SINAMICS G120 List Manual

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #796 background imageLoading...
Page #796 background image
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120 Control Units CU240B-2/CU240E-2
796 List Manual (LH11), 01/2016, A5E33839529
Remedy: - save all parameters (p0977 = 1 or p0971 = 1 or "copy RAM to ROM").
- acknowledge fault (e.g. BI: p2103).
See also: r9776 (SI diagnostics)
F01649 SI P1 (CU): Internal software error
Message class: Hardware/software error (1)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An internal error in the Safety Integrated software on processor 1 has occurred.
Note:
This fault results in a STOP A that cannot be acknowledged.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (switch-off/switch-on).
- re-commission the "Safety Integrated" function and carry out a POWER ON.
- contact Technical Support.
- replace Control Unit.
F01650 SI P1 (CU): Acceptance test required
Message class: Safety monitoring channel has identified an error (10)
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive-integrated "Safety Integrated" function on processor 1 requires an acceptance test.
Note:
This fault results in a STOP A that can be acknowledged.
Fault value (r0949, interpret decimal):
130: Safety parameters for processor 2 not available.
Note:
This fault value is always output when Safety Integrated is commissioned for the first time.
1000: Reference and actual checksum on processor 1 are not identical (booting).
- at least one checksum-checked piece of data is defective.
- safety parameters set offline and loaded into the Control Unit.
2000: Reference and actual checksum on processor 1 are not identical (commissioning mode).
- reference checksum incorrectly entered on processor 1 (p9799 not equal to r9798).
- when de-activating the safety functions, p9501 was not deleted.
2001: Reference and actual checksum on processor 2 are not identical (commissioning mode).
- reference checksum incorrectly entered on processor 2 (p9899 not equal to r9898).
- when de-activating the safety functions, p9501 was not deleted.
2002: Enable of safety-related functions between the processor 1 and processor 2 differ (p9601 not equal to p9801).
2003: Acceptance test is required as a safety parameter has been changed.
2004: An acceptance test is required because a project with enabled safety-functions has been downloaded.
2005: The Safety logbook has identified that a functional safety checksum has changed. An acceptance test is
required.
2010: Enable of safety-related brake control between the two monitoring channels differ (p9602 not equal to p9802).
2020: Error when saving the safety parameters for the processor 2.
9999: Subsequent response of another safety-related fault that occurred when booting that requires an acceptance
test.
Remedy: For fault value = 130:
- carry out safety commissioning routine.
For fault value = 1000:
- again carry out safety commissioning routine.
- replace the memory card or Control Unit.
- Using STARTER, activate the safety parameters for the drive involved (change settings, copy parameters, activate
settings).
For fault value = 2000:
- check the safety parameters on processor 1 and adapt the reference checksum (p9799).

Table of Contents

Other manuals for Siemens SINAMICS G120

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G120 and is the answer not in the manual?

Siemens SINAMICS G120 Specifications

General IconGeneral
Power Range0.37 kW to 250 kW
Output Voltage0 V to Input Voltage
Frequency Range0 Hz to 650 Hz
Enclosure RatingIP20, IP21, IP55
Control ModesV/f control, vector control, servo control
Protection FeaturesOvervoltage, undervoltage, short circuit
Communication InterfacesPROFIBUS, PROFINET, Modbus RTU
Operating Temperature-10°C to +50°C
Cooling MethodAir cooling
Input Voltage200 V to 240 V, 380 V to 480 V, 500 V to 690 V

Related product manuals