EasyManua.ls Logo

Siemens SINAMICS G120 - p0580 Measuring probe input terminal; MT input terminal; p0581 Measuring probe edge; MT edge; p0582 Measuring probe pulses per revolution; MT pulses per rev; p0583 Measuring probe maximum measuring time; MT t_meas max

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
91
2 Parameters
2.2 List of parameters
Description: Sets the input terminal for the measuring probe for speed actual value measurement.
Value: 0: No meas probe
23: DI 3 (T. 8)
Dependency: Refer to: p0581
Note: DI: Digital Input
Description: Sets the edge to evaluate the measuring probe signal for speed actual value measurement.
0: 0/1 edge
1: 1/0 edge
Dependency: Refer to: p0580
Description: Sets the number of pulses per revolution (e.g. for disks with holes).
Description: Sets the maximum measuring time for the measuring probe.
If a new pulse is not received before the maximum measuring time has expired, then the speed actual value in r0586
is set to zero. This timer is re-started with the next pulse.
Dependency: Refer to: r0586
p0580 Measuring probe input terminal / MT input terminal
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 23 0
p0581 Measuring probe edge / MT edge
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Integer16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0 1 0
p0582 Measuring probe pulses per revolution / MT pulses per rev
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 12 1
p0583 Measuring probe maximum measuring time / MT t_meas max
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.040 [s] 10.000 [s] 10.000 [s]