EasyManua.ls Logo

Siemens SINAMICS G120 - p9322[0...7] SI Motion gearbox motor;load numerator (processor 2); SI Mtn gear num P2; p9331[0...3] SI Motion SLS limit values (processor 2); SI Mtn SLS lim P2; p9342 SI Motion act. val. comparison tolerance (crossw.) (processor 2); SI Mtn actV tol P2

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
393
2 Parameters
2.2 List of parameters
Description: Sets the numerator for the gearbox between the motor and the load.
Index: [0] = Gearbox 1
[1] = Gearbox 2
[2] = Gearbox 3
[3] = Gearbox 4
[4] = Gearbox 5
[5] = Gearbox 6
[6] = Gearbox 7
[7] = Gearbox 8
Dependency: Refer to: p9321
Notice: It is not possible to change over the gearbox stages. Gearbox 1 (index 0) is always active.
Note: In the case of encoderless monitoring functions, the pole pair number must be multiplied by the numerator of the
gearbox ratio.
Example:
Gearbox ratio 1:4, pole pair number (r0313) = 2
--> p9321 = 1, p9322 = 8 (4 x 2)
Description: Sets the limit values for the function "Safely Limited Speed" (SLS).
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLS4
Dependency: Refer to: p9363, p9531
Refer to: C01714
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SLS: Safely Limited Speed
Description: Sets the tolerance for the crosswise data comparison of the actual position between processors 1 and 2.
Dependency: Refer to: p9542
Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: For a linear axis, the tolerance is internally limited to 10 mm.
For a "linear axis with rotating motor" and factory setting of p9320, p9321 and p9322, the factory setting of p9342
corresponds to a position tolerance of 36 ° on the motor side.
p9322[0...7] SI Motion gearbox motor/load numerator (processor 2) / SI Mtn gear num P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 2147000000 1
p9331[0...3] SI Motion SLS limit values (processor 2) / SI Mtn SLS lim P2
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.01 [rpm] 100000.00 [rpm] 2000.00 [rpm]
p9342 SI Motion act. val. comparison tolerance (crossw.) (processor 2) / SI Mtn actV tol P2
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.0010 [°] 360.0000 [°] 12.0000 [°]