2 Parameters
2.2 List of parameters
Description: Displays the number of inputs and outputs.
Index: [0] = Number of digital inputs
[1] = Number of digital outputs
[2] = Number of digital input/outputs bidirectional
[3] = Number of analog inputs
[4] = Number of analog outputs
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p0795.x = 1) to terminal mode (p0795.x = 0).
Note: AI: Analog Input
DI: Digital Input
T: Terminal
Description: Displays the actual value at the digital inputs.
This means that the actual input signal can be checked at terminal DI x or DI/DO x prior to switching from the
simulation mode (p0795.x = 1) to terminal mode (p0795.x = 0).
Note: AI: Analog Input
DI: Digital Input
T: Terminal
r0720[0...4] CU number of inputs and outputs / CU I/O count
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2119
Min Max Factory setting
- - -
r0721 CU digital inputs terminal actual value / CU DI term act val
CU240B-2
CU240B-2_DP
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2202, 2220,
2221, 2255, 2256
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) High Low -
01 DI 1 (T. 6) High Low -
02 DI 2 (T. 7) High Low -
03 DI 3 (T. 8) High Low -
11 DI 11 (T. 3, 4) AI 0 High Low -
r0721 CU digital inputs terminal actual value / CU DI term act val
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2201, 2202, 2220,
2221, 2255, 2256
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (T. 5) High Low -
01 DI 1 (T. 6) High Low -
02 DI 2 (T. 7) High Low -
03 DI 3 (T. 8) High Low -
04 DI 4 (T. 16) High Low -
05 DI 5 (T. 17) High Low -
11 DI 11 (T. 3, 4) AI 0 High Low -
12 DI 12 (T. 10, 11) AI 1 High Low -