Siemens SINAMICS G120 - p9546 SI Motion SSM velocity limit (processor 1); SI Mtn SSM v_limP1; p9547 SI Motion SSM velocity hysteresis (processor 1); SI Mtn SSM hyst P1; p9548 SI Motion SAM actual velocity tolerance (processor 1); SI mtn SAM tol P1; p9551 SI Motion SLS changeover delay time (processor 1); SI Mtn SLS t P1

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
409
2 Parameters
2.2 List of parameters
Description: Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
Caution: The following applies for p9506 = 3:
The "SAM" function is switched out if the selected threshold value is undershot.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity hysteresis for the SSM feedback signal to detect standstill (n < nx).
Dependency: Refer to: C01711
Note: The velocity hysteresis is effective only if the function is enabled (p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity tolerance for the "SAM" function.
Dependency: Refer to: C01706
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
Description: Sets the delay time for the SLS changeover for the function "safely limited speed" (SLS).
When transitioning from a higher to a lower safely limited velocity/speed stage, within this delay time, the "old"
velocity stage remains active.
Even if SLS is activated from the state "SLS in active", then this delay is still applied.
Note: SLS: Safely Limited Speed
p9546 SI Motion SSM velocity limit (processor 1) / SI Mtn SSM v_limP1
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.00 [rpm] 100000.00 [rpm] 20.00 [rpm]
p9547 SI Motion SSM velocity hysteresis (processor 1) / SI Mtn SSM hyst P1
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.0010 [rpm] 500.0000 [rpm] 10.0000 [rpm]
p9548 SI Motion SAM actual velocity tolerance (processor 1) / SI mtn SAM tol P1
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [rpm] 120000.00 [rpm] 300.00 [rpm]
p9551 SI Motion SLS changeover delay time (processor 1) / SI Mtn SLS t P1
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2819, 2820
Min Max Factory setting
0.00 [ms] 600000.00 [ms] 100.00 [ms]