SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
409
2 Parameters
2.2 List of parameters
Description: Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
Caution: The following applies for p9506 = 3:
The "SAM" function is switched out if the selected threshold value is undershot.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity hysteresis for the SSM feedback signal to detect standstill (n < nx).
Dependency: Refer to: C01711
Note: The velocity hysteresis is effective only if the function is enabled (p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity tolerance for the "SAM" function.
Dependency: Refer to: C01706
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
Description: Sets the delay time for the SLS changeover for the function "safely limited speed" (SLS).
When transitioning from a higher to a lower safely limited velocity/speed stage, within this delay time, the "old"
velocity stage remains active.
Even if SLS is activated from the state "SLS in active", then this delay is still applied.
Note: SLS: Safely Limited Speed
p9546 SI Motion SSM velocity limit (processor 1) / SI Mtn SSM v_limP1
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.00 [rpm] 100000.00 [rpm] 20.00 [rpm]
p9547 SI Motion SSM velocity hysteresis (processor 1) / SI Mtn SSM hyst P1
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2823
Min Max Factory setting
0.0010 [rpm] 500.0000 [rpm] 10.0000 [rpm]
p9548 SI Motion SAM actual velocity tolerance (processor 1) / SI mtn SAM tol P1
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
0.00 [rpm] 120000.00 [rpm] 300.00 [rpm]
p9551 SI Motion SLS changeover delay time (processor 1) / SI Mtn SLS t P1
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2819, 2820
Min Max Factory setting
0.00 [ms] 600000.00 [ms] 100.00 [ms]