EasyManua.ls Logo

Siemens SINAMICS G120 - r9798 SI actual checksum SI parameters (processor 1); SI act chksm P1; p9799 SI setpoint checksum SI parameters (processor 1); SI setp_chksm P1; p9801 SI enable functions integrated in the drive (processor 2); SI enable fct P2

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
441
2 Parameters
2.2 List of parameters
Description: Displays the checksum for the Safety Integrated parameters checked using checksums on processor 1 (actual
checksum).
Dependency: Refer to: p9799, r9898
Description: Sets the checksum for the Safety Integrated parameters checked using checksums on processor 1 (setpoint
checksum).
Dependency: Refer to: r9798, p9899
Description: Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
r9798 SI actual checksum SI parameters (processor 1) / SI act chksm P1
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
- - -
p9799 SI setpoint checksum SI parameters (processor 1) / SI setp_chksm P1
PM230_STO
PM240
PM250
PM260
CU240E-2
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2800
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p9801 SI enable functions integrated in the drive (processor 2) / SI enable fct P2
PM230_STO
CU240E-2_DP
CU240E-2 PN
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- - 0000 bin