Siemens SINAMICS G120 - p1967 Speed_ctrl_opt dynamic factor; n_opt dyn_factor; r1968 Speed_ctrl_opt dynamic factor actual; n_opt dyn_fact act; r1969 Speed_ctrl_opt moment of inertia determined; n_opt M_inert det; r1970[0...1] Speed_ctrl_opt vibration test vibration frequency determined; n_opt f_vib det

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
269
2 Parameters
2.2 List of parameters
Description: Sets the dynamic response factor for speed controller optimization.
After optimization, the dynamic response achieved is displayed in r1968.
Dependency: Refer to: p1959, r1968
Refer to: F07985
Note: For a rotating measurement, this parameter can be used to optimize the speed controller.
p1967 = 100 % --> speed controller optimization according to a symmetric optimum.
p1967 > 100 % --> optimization with a higher dynamic response (Kp higher, Tn lower).
If the actual dynamic response (see r1968) is significantly reduced with respect to the required dynamic response
(p1967), then this can be as a result of mechanical load oscillations. If, in spite of this load behavior, a higher dynamic
response is required, then the oscillation test (p1959.4 = 0) should be de-activated and the measurement repeated.
Description: Displays the dynamic factor which is actually achieved for the vibration test
Dependency: Refer to: p1959, p1967
Refer to: F07985
Note: This dynamic factor only refers to the control mode of the speed controller set in p1960.
Description: Displays the determined moment of inertia of the drive.
After it has been determined, the value is transferred to p0341, p0342.
Dependency: IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
Refer to: p0341, p0342, p1959
Refer to: F07984
Description: Displays the vibration frequencies determined by the vibration test.
Index: [0] = Frequency low
[1] = Frequency high
Dependency: Refer to: p1959
Refer to: F07985
p1967 Speed_ctrl_opt dynamic factor / n_opt dyn_factor
Access level: 3 Calculated: p0340 = 1 Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
1 [%] 400 [%] 100 [%]
r1968 Speed_ctrl_opt dynamic factor actual / n_opt dyn_fact act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [%] - [%] - [%]
r1969 Speed_ctrl_opt moment of inertia determined / n_opt M_inert det
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: 25_1 Unit selection: p0100 Func. diagram: -
Min Max Factory setting
- [kgm²] - [kgm²] - [kgm²]
r1970[0...1] Speed_ctrl_opt vibration test vibration frequency determined / n_opt f_vib det
Access level: 4 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
- [Hz] - [Hz] - [Hz]