Siemens SINAMICS G120 - p9351 SI Motion SLS changeover delay time (processor 2); SI Mtn SLS t P2; p9356 SI Motion pulse suppression delay time (processor 2); SI Mtn IL t_del P2; p9358 SI Motion acceptance test mode time limit (processor 2); SI Mtn acc t P2; p9360 SI Motion pulse suppression shutdown speed (processor 2); SI Mtn IL n_sh P2

Siemens SINAMICS G120
924 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
395
2 Parameters
2.2 List of parameters
Description: Sets the delay time for the SLS changeover for the function "safely limited speed" (SLS).
When transitioning from a higher to a lower safely limited velocity/speed stage, within this delay time, the "old"
velocity stage remains active.
Even if SLS is activated from the state "SLS in active", then this delay is still applied.
Dependency: Refer to: p9551
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SLS: Safely Limited Speed
Description: Sets the delay time for STOP A after STOP B / SS1.
Dependency: Refer to: p9360, p9556
Refer to: C01701
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
SS1: Safe Stop 1
Description: Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency: Refer to: p9558
Refer to: C01799
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The set time is rounded internally to an integer multiple of the monitoring clock cycle.
Description: Sets the shutdown speed for the pulse suppression.
Below this speed "standstill" is assumed and for STOP B / SS1, the pulses are suppressed (by changing to STOP A).
Dependency: Refer to: p9356, p9560
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
p9351 SI Motion SLS changeover delay time (processor 2) / SI Mtn SLS t P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2819, 2820
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9356 SI Motion pulse suppression delay time (processor 2) / SI Mtn IL t_del P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 2819
Min Max Factory setting
0.00 [µs] 3600000000.00 [µs] 600000000.00 [µs]
p9358 SI Motion acceptance test mode time limit (processor 2) / SI Mtn acc t P2
PM240
PM250
PM260
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
5000000.00 [µs] 100000000.00 [µs] 40000000.00 [µs]
p9360 SI Motion pulse suppression shutdown speed (processor 2) / SI Mtn IL n_sh P2
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: C(95) Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: -
Min Max Factory setting
10.00 [rpm] 6000.00 [rpm] 10.00 [rpm]