SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
331
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the setpoint 1 of the technology controller.
Dependency: Refer to: p2254, p2255
Description: Sets the signal source for the setpoint 2 of the technology controller.
Dependency: Refer to: p2253, p2256
Description: Sets the scaling for the setpoint 1 of the technology controller.
Dependency: Refer to: p2253
Description: Sets the scaling for the setpoint 2 of the technology controller.
Dependency: Refer to: p2254
Description: Sets the ramp-up time of the technology controller.
Dependency: Refer to: p2258
Note: The ramp-up time is referred to 100 %.
p2253[0...n] CI: Technology controller setpoint 1 / Tec_ctrl setp 1
Access level: 2 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2254[0...n] CI: Technology controller setpoint 2 / Tec_ctrl setp 2
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: U, T Scaling: PERCENT Dyn. index: CDS, p0170
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
- - 0
p2255 Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [%] 100.00 [%] 100.00 [%]
p2256 Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [%] 100.00 [%] 100.00 [%]
p2257 Technology controller ramp-up time / Tec_ctrl t_ramp-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: U, T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7958
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]