SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
505
2 Parameters
2.2 List of parameters
Description: Sets the signal source for the "accept setting value" signal of instant PT1 1 of the smoothing element.
Description: Sets the smoothing time constant T in milliseconds of instance PT1 1 of the smoothing element.
Description: Display parameter for the smoothed output quantity Y of instance PT1 1 of the smoothing element.
Description: Setting parameter for the run-time group in which instance PT1 1 of the smoothing element is to be called.
Value: 5: Run-time group 5
6: Run-time group 6
9999: Do not calculate
Description: Setting parameter for the run sequence of instance PT1 1 within the run-time group set in p20254.
Note: The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
Description: Sets the signal source of input quantity X and of setting value SV of instance INT 0 of the integrator.
p20251 BI: PT1 1 accept setting value S / PT1 1 acc set val
Access level: 3 Calculated: - Data type: U32 / Binary
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7262
Min Max Factory setting
- - 0
p20252 PT1 1 smoothing time constant in ms / PT1 1 T_smooth ms
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7262
Min Max Factory setting
0.00 340.28235E36 0.00
r20253 CO: PT1 1 output Y / PT1 1 output Y
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7262
Min Max Factory setting
- - -
p20254 PT1 1 run-time group / PT1 1 RTG
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7262
Min Max Factory setting
5 9999 9999
p20255 PT1 1 run sequence / PT1 1 RunSeq
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7262
Min Max Factory setting
0 32000 680
p20256[0...1] CI: INT 0 inputs / INT 0 inputs
Access level: 3 Calculated: - Data type: U32 / FloatingPoint32
Can be changed: T Scaling: PERCENT Dyn. index: -
Unit group: - Unit selection: - Func. diagram: 7264
Min Max Factory setting
- - 0