2 Parameters
2.6 Quick commissioning (p0010 = 1)
SINAMICS G120 Control Units CU240B-2/CU240E-2
554 List Manual (LH11), 01/2016, A5E33839529
If p0010 = 1 is selected, p0003 (user access level) can be used to select the parameters that
are to be accessed.
At the end of the quick commissioning, set p3900 = 1 to perform the required motor
calculations and reset all other parameters (not included in p0010 = 1) to their default settings.
p1300 Open-loop/closed-loop control operating mode 2 C(1)T
p1500 Torque setpoint selection 2 C(1)T
p1900 Motor data identification and rotating measurement 2 C(1)T
p1905 Parameter tuning selection 1 C(1)T
p2196 Torque utilization scaling 1 C(1,3)UT
p3900 Completion of quick commissioning 1 C(1)
Note
This only applies for the quick commissioning.
Table 2-7 Quick commissioning (p0010 = 1), continued
Par. no. Name Access level Can be
changed