5.4.3 Start quick commissioning and select the application class
Starting quick commissioning
Preconditions
The power supply is switched on.
The operator panel displays setpoints and actual values.
Procedure
Press the ESC key.
Press one of the arrow keys until the BOP-2 displays the "SETUP" menu.
To start quick commissioning, in the "SETUP" menu, press the OK key.
If you wish to restore all of the parameters to the factory setting before the quick commissioning,
proceed as follows:
1. Press the OK key.
2. Switchover the display using an arrow key: nO → YES
3. Press the OK key.
When selecting an application class, the converter assigns the motor control with the
appropriate default settings:
Standard Drive Control (Page 114)
Dynamic Drive Control (Page 116)
Expert (Page 118)
Depending on the particular Power Module, the converter skips selecting the application
class. If the BOP-2 does not display step DRV APPL, then continue commissioning as
described under "Expert".
63
6(783
5(6(7
3
'59$33/
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120XA converter
112 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB