p1051[0...n] CI: Speed limit RFG positive direction of rotation / n_limit RFG pos
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3050
Min:
-
Max:
-
Factory setting:
1083[0]
Description: Sets the signal source for the speed limit of the positive direction on the ramp-function generator input.
Note
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
p1052[0...n] CI: Speed limit RFG negative direction of rotation / n_limit RFG neg
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3050
Min:
-
Max:
-
Factory setting:
1086[0]
Description: Sets the signal source for the speed limit of the negative direction on the ramp-function generator input.
Note
The OFF3 ramp-down time (p1135) is effective when the limit is reduced.
p1055[0...n] BI: Jog bit 0 / Jog bit 0
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501, 3030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for jog 1.
Recommendation: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: See also: p0840, p1058
NOTICE
The drive is enabled for jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that was used to switch on can also be used to switch off again.
p1056[0...n] BI: Jog bit 1 / Jog bit 1
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501, 3030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for jog 2.
Recommendation: When the setting for this binector input is changed, the motor can only be switched on by means of an appropriate
signal change of the source.
Dependency: See also: p0840, p1059