EasyManua.ls Logo

Siemens SINAMICS G120XA - CU Analog Outputs Characteristic Value X1; CU AO Char X1; CU Analog Outputs Characteristic Value Y1; CU AO Char Y1

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Note
When changing p0776, the parameters of the scaling characteristic (p0777, p0778, p0779, p0780) are overwritten with
the following default values:
For p0776 = 0, p0777 is set to 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
For p0776 = 1, p0777 is set to 0.0 %, p0778 = 0.0 V, p0779 = 100.0 % and p0780 to 10.0 V.
For p0776 = 2, p0777 is set to 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 % and p0780 to 20.0 mA.
p0777[0...2] CU analog outputs characteristic value x1 / CU AO char x1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-1000.00 [%]
Max:
1000.00 [%]
Factory setting:
0.00 [%]
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the x coordinate (percentage) of the 1st value pair of the characteristic.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency: See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.
p0778[0...2] CU analog outputs characteristic value y1 / CU AO char y1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9572
Min:
-20.000 [V]
Max:
20.000 [V]
Factory setting:
0.000 [V]
Description: Sets the scaling characteristic for the analog outputs.
The scaling characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 1st value pair of the
characteristic.
Index: [0] = AO0 (X132 12/13)
[1] = AO1 (X131 26/X132 27)
[2] = Reserved
Dependency: The unit of this parameter (V or mA) depends on the analog output type.
See also: p0776
NOTICE
This parameter is automatically overwritten when changing p0776 (type of analog outputs).
Note
The parameters for the characteristic do not have a limiting effect.