Dependency: See also: p2257
Note
The ramp-down time is referred to 100 %.
r2260 CO: Technology controller setpoint after ramp-function generator / Tec_ctr set aftRFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Sets the setpoint after the ramp-function generator of the technology controller.
p2261 Technology controller setpoint filter time constant / Tec_ctrl set T
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
0.000 [s]
Description: Sets the time constant for the setpoint filter (PT1) of the technology controller.
r2262 CO: Technology controller setpoint after filter / Tec_ctr set aftFlt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the smoothed setpoint after the setpoint filter (PT1) of the technology controller.
p2263 Technology controller type / Tec_ctrl type
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0
Max:
1
Factory setting:
0
Description: Sets the type of technology controller.
Value: 0: D component in the actual value signal
1: D component in system deviation
p2264[0...n] CI: Technology controller actual value / Tec_ctrl act val
Access level: 2 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the actual value of the technology controller.