6.2.4 Communication via USS
6.2.4.1 Activating communication via fieldbus
Function description
Procedure
Proceed as follows to activate communication via USS:
1. Start quick commissioning.
2. In the first steps of the quick commissioning, confirm all of the values that have already been
set.
3. Select one of the following default settings:
54: "USS control"
55: "USS control local/remote"
Default setting of the interfaces (Page 82)
4. In the next steps of the quick commissioning, confirm all additional values that have already
been set.
5. Exit quick commissioning.
You have activated communication via USS.
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 167