r3996[0...1] Parameter write inhibit status / Par_write inhib st
Access level: 3 Calculated: - Data type: Unsigned8
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays whether writing to parameters is inhibited.
r3996[0] = 0:
Parameter write not inhibited.
0 < r3996[0] < 100:
Parameter write inhibited. The value shows how the calculations are progressing.
Index: [0] = Progress calculations
[1] = Cause
Note
For index 1:
Only for internal Siemens troubleshooting.
r4022.0...3 CO/BO: PM330 digital inputs status / PM330 DI status
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status of the digital inputs of the PM330 power unit.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: See also: r4023
Note
DI: Digital Input
r4023.0...3 CO/BO: PM330 digital inputs status inverted / PM330 DI stat inv
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the inverted status of the digital inputs of Power Module 330 (PM330).
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X9.3, external alarm) High Low -
01 DI 1 (X9.4, external fault) High Low -
02 DI 2 (X9.5, Emergency Off category 0) High Low -
03 DI 3 (X9.6, Emergency Off category 1) High Low -
Dependency: See also: r4022
Note
DI: Digital Input
Parameters
7.3 Parameters
SINAMICS G120XA converter
660 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB