p2127[0...19] Change acknowledge mode mode / Chng ackn mode
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8075
Min:
1
Max:
2
Factory setting:
1
Description: Sets the acknowledge mode for selected fault.
Value: 1: Acknowledgment only using POWER ON
2: Ack IMMEDIATELY after the fault cause has been removed
Dependency: Selects the faults and sets the required acknowledge mode realized under the same index
See also: p2126
NOTICE
It is not possible to re-parameterize the acknowledge mode for a fault in the following cases:
- fault number does not exist (exception value = 0).
- Message type is not "fault" (F).
- Acknowledge mode is not permissible for the set fault number.
Note
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has been
resolved.
The acknowledge mode can only be changed for faults with the appropriate identification.
Example:
F12345 and acknowledge mode = IMMEDIATELY (POWER ON)
--> The acknowledge mode can be changed from IMMEDIATELY to POWER ON.
p2128[0...15] Faults/alarms trigger selection / F/A trigger sel
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8070
Min:
0
Max:
65535
Factory setting:
0
Description: Sets the faults/alarms for which a trigger signal should be generated in r2129.0...15.
Dependency: If the fault/alarm set in p2128[0...15] occurs, then the particular binector output r2129.0...15 is set.
See also: r2129
r2129.0...15 CO/BO: Faults/alarms trigger word / F/A trigger word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8070
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the trigger signals of the faults/alarms set in p2128[0...15].
Bit field: Bit Signal name 1 signal 0 signal FP
00 Trigger signal p2128[0] ON OFF -
01 Trigger signal p2128[1] ON OFF -
02 Trigger signal p2128[2] ON OFF -
03 Trigger signal p2128[3] ON OFF -
04 Trigger signal p2128[4] ON OFF -
05 Trigger signal p2128[5] ON OFF -
06 Trigger signal p2128[6] ON OFF -
Parameters
7.3 Parameters
SINAMICS G120XA converter
584 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB