p2153[0...n] Speed actual value filter time constant / n_act_filt T
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8010
Min:
0 [ms]
Max:
1000000 [ms]
Factory setting:
0 [ms]
Description: Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and signals.
Dependency: See also: r2169
p2155[0...n] Speed threshold 2 / n_thresh val 2
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
900.00 [rpm]
Description: Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency: See also: p2140, r2197
p2156[0...n] On delay comparison value reached / t_on cmpr val rchd
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8010
Min:
0.0 [ms]
Max:
10000.0 [ms]
Factory setting:
0.0 [ms]
Description: Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency: See also: p2141, p2142, r2199
p2161[0...n] Speed threshold 3 / n_thresh val 3
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010, 8011
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
5.00 [rpm]
Description: Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency: See also: p2150, r2199
p2162[0...n] Hysteresis speed n_act > n_max / Hyst n_act>n_max
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
0.00 [rpm]
Max:
60000.00 [rpm]
Factory setting:
0.00 [rpm]
Description: Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 591