Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3324[0...n] Fluid flow machine power point 3 / Fluid_mach P3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
77.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 3 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3325, p3326, p3327, p3328, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3325[0...n] Fluid flow machine speed point 3 / Fluid_mach n3
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
50.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 3 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3324, p3326, p3327, p3328, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3326[0...n] Fluid flow machine power point 4 / Fluid_mach P4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
92.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 4 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3327, p3328, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.