When must the fan unit be replaced?
A defective fan in operation results in an overtemperature condition of the converter. For
example, the following messages indicate that the fan unit is defective:
A05002 (air intake overtemperature)
A05004 (rectifier overtemperature)
F30004 (heat sink overtemperature)
F30024 (temperature model overtemperature)
F30025 (chip overtemperature)
F30035 (air intake overtemperature)
F30037 (rectifier overtemperature)
Precondition
Switch off the converter power supply before replacing the fan unit.
WARNING
Electric shock as a result of a residual charge in power components
After the power supply has been switched off, it takes up to 5 minutes until the capacitors in
the converter have discharged so that the residual charge is at a non-hazardous level.
Therefore, touching the converter immediately after powering off can result in electric shock
due to residual charge in the power components.
Check the voltage at the converter connections before you replace the fan unit.
Corrective maintenance
10.2 Replacing spare parts
SINAMICS G120XA converter
834 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB