p29527 Multi-pump control interlocking time / Mpc t_interl
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0 [s]
Max:
650 [s]
Factory setting:
0 [s]
Description: Interlocking time during which, following the connection or disconnection of a motor, no further motors are connected
or disconnected using the multi-control control. This avoids duplicate switching operations.
p29528 Multi-pump control switch-out speed offset / Mpc sw_out offset
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
0.0 [rpm]
Max:
21000.0 [rpm]
Factory setting:
100.0 [rpm]
Description: Sets the speed offset which pluses p1080 as the speed threshold.
If the system deviation of the technology controller has exceeded the threshold p29523 for p29525s (or exceeded the
threshold p29526) and the motor has reached the speed threshold p1080+p29528, a motor will be switched out.
r29529.0...7 CO/BO: Multi-pump control status word / Mpc ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status word of the multi-pump control
Bit field: Bit Signal name 1 signal 0 signal FP
00 Start motor 1 Yes No -
01 Start motor 2 Yes No -
02 Start motor 3 Yes No -
03 Start motor 4 Yes No -
04 Switch-in/switch-out active Yes No -
05 All motors active Yes No -
06 Cycling not possible Yes No -
07 Alarm active Yes No -
p29530[0...3] Multi-pump control absolute operating hours / Mpc op_hrs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [h]
Max:
340.28235E36 [h]
Factory setting:
0.00 [h]
Description: Displays the total operating hours for motors.
The display can only be reset to zero.
Index: [0] = motor 1 operating hours
[1] = motor 2 operating hours
[2] = motor 3 operating hours
[3] = motor 4 operating hours
Parameters
7.3 Parameters
SINAMICS G120XA converter
708 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB