Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
p0254[0...n] Operating hours counter power unit fan inside the converter / PU inner fan t_op
CUG120XA_USS
(PM330)
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: PDS, p0120
Unit group: - Unit selection: - Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description: Displays the power unit fan operating hours of the internal fan in the power unit.
The number of hours operated can only be reset to 0 in this parameter (e.g. after a fan has been replaced).
Dependency: See also: A30042
Note
For liquid-cooled chassis power units, the operating hours of the inner fan are displayed in p0251 and not in p0254.
p0287[0...1] Ground fault monitoring thresholds / Gnd flt threshold
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.0 [%]
Max:
100.0 [%]
Factory setting:
[0] 6.0 [%]
[1] 16.0 [%]
Description: Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index: [0] = Threshold at which precharging starts
[1] = Threshold at which precharging stops
Dependency: See also: p1901
See also: F30021
Note
This parameter is only relevant for chassis power units.
r0289 CO: Maximum power unit output current / PU I_outp max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2002 Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
- [Arms]
Max:
- [Arms]
Factory setting:
- [Arms]
Description: Displays the actual maximum output current of the power unit taking into account derating factors.
p0290 Power unit overload response / PU overld response
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8021
Min:
0
Max:
13
Factory setting:
2
Parameters
7.3 Parameters
SINAMICS G120XA converter