p1233[0...n] DC braking time / DCBRK time
CUG120XA_USS (DC
braking)
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 7017
Min:
0.0 [s]
Max:
3600.0 [s]
Factory setting:
1.0 [s]
Description: Sets the DC braking time (as fault response).
Dependency: See also: p1230, p1231, p1232, p1234, r1239
p1234[0...n] Speed at the start of DC braking / DCBRK n_start
CUG120XA_USS (DC
braking)
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 7017
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
210000.00 [rpm]
Description: Sets the starting speed for DC braking.
If the actual speed falls below this threshold, then DC braking is activated.
Dependency: See also: p1230, p1231, p1232, p1233, r1239
r1239.8...13 CO/BO: DC braking status word / DCBRK ZSW
CUG120XA_USS (DC
braking)
Access level: 2 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Status word of the DC braking.
Bit field: Bit Signal name 1 signal 0 signal FP
08 DC braking active Yes No 7017
10 DC braking ready Yes No 7017
11 DC braking selected Yes No -
12 DC braking selection internally inhibited Yes No -
13 DC braking for OFF1/OFF3 Yes No -
Dependency: See also: p1231, p1232, p1233, p1234
Note
For bit 12, 13:
Only effective for p1231 = 14.
p1240[0...n] Vdc controller configuration (vector control) / Vdc ctr config vec
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 6220, 6827
Min:
0
Max:
3
Factory setting:
1
Description: Sets the controller configuration of the DC link voltage (Vdc controller) in the closed-loop control mode. For U/f control:
see p1280.
Value: 0: Inhibit Vdc ctrl
1: Enable Vdc_max controller
2: Enable Vdc_min controller (kinetic buffering)
3: Enable Vdc_min controller and Vdc_max controller