p1263 Debypass delay time / Debypass t_del
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.000 [s]
Max:
300.000 [s]
Factory setting:
1.000 [s]
Description: Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Dependency: The "Bypass" function is only available for induction motors.
p1264 Bypass delay time / Bypass t_del
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.000 [s]
Max:
300.000 [s]
Factory setting:
1.000 [s]
Description: Sets the delay time for switching to line operation for a non-synchronized bypass.
Dependency: The "Bypass" function is only available for induction motors.
p1265 Bypass speed threshold / Bypass n_thresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
1480.00 [rpm]
Description: Sets the speed threshold to activate the bypass.
Dependency: The "Bypass" function is only available for induction motors.
If the drive setpoint speed is entered via a motorized potentiometer, then the configuration bit p1030.4 should be set
in order to ensure the bypass via speed threshold function.
Note
When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
The bypass speed threshold is only effective for positive directions of rotation. If the drive connected to the line supply
requires negative speeds, then this can be achieved using p1820 (direction of rotation reversal).
p1266 BI: Bypass control command / Bypass command
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the control command to the bypass.
Dependency: The "Bypass" function is only available for induction motors.
p1267 Bypass changeover source configuration / Chngov_src config
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the cause that should initiate the bypass.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 503