p0809[0...2] Copy Command Data Set CDS / Copy CDS
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8560
Min:
0
Max:
3
Factory setting:
0
Description: Copies one Command Data Set (CDS) into another.
Index: [0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Dependency: See also: r3996
NOTICE
When the command data sets are copied, short-term communication interruptions may occur.
Note
Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0810 BI: Command data set selection CDS bit 0 / CDS select., bit 0
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8560
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to select the Command Data Set bit 0 (CDS bit 0).
Dependency: See also: r0050, p0811, r0836
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
p0811 BI: Command data set selection CDS bit 1 / CDS select., bit 1
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8560
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to select the Command Data Set bit 1 (CDS bit 1).
Dependency: See also: r0050, p0810, r0836
Note
The Command Data Set selected using the binector inputs is displayed in r0836.
The currently effective command data set is displayed in r0050.
A Command Data Set can be copied using p0809.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 445