Siemens SINAMICS G120XA - CU Analog Inputs Dead Zone; CU AI Dead Zone; CU Analog Inputs Wire Breakage Monitoring Delay Time; CU Analog Inputs Wire Breakage Monitoring Response Threshold

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
The parameters for the characteristic do not have a limiting effect.
p0761[0...3] CU analog inputs wire breakage monitoring response threshold / CU WireBrkThresh
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568
Min:
0.00
Max:
20.00
Factory setting:
2.00
Description: Sets the response threshold for the wire breakage monitoring of the analog inputs.
The unit for the parameter value depends on the set analog input type.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Dependency: For the following analog input type, the wire breakage monitoring is active:
p0756[0...1] = 1 (unipolar voltage input monitored (+2 V ... +10 V)), unit [V]
p0756[0...2] = 3 (unipolar current input monitored (+4 mA ... +20 mA)), unit [mA]
p0756[3]: Wire breakage monitoring is not supported for this analog input.
See also: p0756
Note
AI: Analog Input
When p0761 = 0, wire breakage monitoring is not carried out.
p0762[0...3] CU analog inputs wire breakage monitoring delay time / CU wire brk t_del
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568
Min:
0 [ms]
Max:
1000 [ms]
Factory setting:
100 [ms]
Description: Sets the delay time for the wire breakage monitoring of the analog inputs.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
AI: Analog Input
p0764[0...3] CU analog inputs dead zone / CU AI dead zone
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2251
Min:
0.000
Max:
20.000
Factory setting:
0.000
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 435