p0335[0...n] Motor cooling type / Mot cool type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: C2(1), T Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
128
Factory setting:
0
Description: Sets the motor cooling system used.
Value: 0: Natural ventilation
1: Forced cooling
2: Liquid cooling
128: No fan
Dependency: For 1LA7 motors (p0300), the parameter is pre-set as a function of p0307 and p0311.
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
The parameter influences the thermal 3-mass motor model.
1LA7 motors, frame size 56 are operated without fan.
p0340[0...n] Automatic calculation motor/control parameters / Calc auto par
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
5
Factory setting:
0
Description: Setting to automatically calculate motor parameters and U/f open-loop and closed-loop control parameters from the
rating plate data.
Value: 0: No calculation
1: Complete calculation
2: Calculation of equivalent circuit diagram parameters
3: Calculation of closed-loop control parameters
4: Calculation of controller parameters
5: Calculation of technological limits and threshold values
Parameters
7.3 Parameters
SINAMICS G120XA converter
398 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB