2.6.3 Sine-wave filter
The sine-wave filter limits the voltage gradient and the capacitive recharging currents which
generally occur in inverter operation. Therefore, when a sine-wave filter is used, significantly
longer screened motor cables are possible and the motor lifetime reaches the same values
which are achieved when the motor is connected directly to the mains.
Maximum permissible motor cable length (Page 64)
When using sine-wave filters, observe the following restrictions:
For rated power up to 90 kW, the pulse frequency should not exceed 8 kHz; for rated power
above 90 kW, the pulse frequency should be 4 kHz.
The maximum permissible output frequency is limited to 150 Hz.
Note
Sine-wave filters are available as optional components for converters of frame sizes FSD to
FSG.
Article number
Converter variants Sine-wave filter
Frame size Rated power (kW) Article number
FSD 18.5 6SL3202-0AE24-6SA0
22
30 6SL3202-0AE26-2SA0
37 6SL3202-0AE28-8SA0
45
FSE 55 6SL3202-0AE31-5SA0
FSF 75
90 6SL3202-0AE31-8SA0
110 6SL3000-2CE32-3AA0
132
FSG 160 6SL3000-2CE32-8AA0
200 6SL3000-2CE33-3AA0
250 6SL3000-2CE34-1AA0
Special restrictions for converter FSG
When connecting 400 V converter FSG with sine-wave filters, set parameters as follows:
Parameter 6SL3000-2CE32-8AA0 6SL3000-2CE33-3AA0 6SL3000-2CE34-1AA0
p0230 4 4 4
p0233 [mH] 0.25 0.2 0.15
p0234 [µF] 28.2 42.3 56.4
Description
2.6 Optional components
SINAMICS G120XA converter
34 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB