8.5 Write protection
Overview
The write protection prevents unauthorized changing of the converter settings.
Function description
Write protection is applicable for all user interfaces:
Operator panel BOP-2 and IOP‑2
SINAMICS G120 Smart Access
Parameter changes via fieldbus
No password is required for write protection.
Activate and deactivate write protection
Parameter
r7760 Write protection/know-how protection status
.00 1 signal: Write protection active
p7761 Write protection (factory setting: 0)
0: Deactivate write protection
1: Activate write protection
Parameters
Table 8-2 Parameters that can be changed with active write protection
Number Name
p0003 Access level / Acc_level
p0010 Drive commissioning parameter filter / Drv comm par_filt
p0124[0...n] CU detection using LED / CU detect LED
p0970 Reset drive parameters / Drive par reset
p0971 Save parameters / Sav par
p0972 Drive unit reset / Drv_unit reset
p2111 Alarm counter / Alarm counter
p3950 Service parameter / Serv par
p3981 Acknowledge drive object faults / Ackn DO faults
p3985 Master control mode selection / PcCtrl mode select
p7761 Write protection / Write protection
p8805 Identification and Maintenance 4 Configuration / I&M 4 Config
p8806[0...53] Identification and Maintenance 1 / I&M 1
p8807[0...15] Identification and Maintenance 2 / I&M 2
p8808[0...53] Identification and Maintenance 3 / I&M 3
p8809[0...53] Identification and Maintenance 4 / I&M 4
Saving the settings and series commissioning
8.5 Write protection
SINAMICS G120XA converter
736 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB