Note
Example:
r0964[0] = 42 --> SIEMENS
r0964[1] = device type, see below
r0964[2] = 403 --> first part of the firmware version V04.03 (for second part, refer to index 6)
r0964[3] = 2010 --> year 2010
r0964[4] = 1705 --> 17th of May
r0964[5] = 2 --> 2 drive objects
r0964[6] = 200 --> second part, firmware version (complete version: V04.03.02.00)
Device type:
r0964[1] = 5700 --> SINAMICS G120 CU230P-2_DP
r0964[1] = 5701 --> SINAMICS G120 CU230P-2_PN
r0964[1] = 5702 --> SINAMICS G120 CU230P-2_CAN
r0964[1] = 5703 --> SINAMICS G120 CU230P-2_HVAC
r0964[1] = 5705 --> SINAMICS G120 CU230P-2_BT
p0969 System runtime relative / t_System relative
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8050, 8060
Min:
0 [ms]
Max:
4294967295 [ms]
Factory setting:
0 [ms]
Description: Displays the system runtime in ms since the last POWER ON.
Note
The value in p0969 can only be reset to 0.
The value overflows after approx. 49 days.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
p0970 Reset drive parameters / Drive par reset
Access level: 1 Calculated: - Data type: Unsigned16
Can be changed: C2(1, 30) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
300
Factory setting:
0
Description: The parameter is used to initiate the reset of the drive parameters.
Parameters p0100, p0205 are not reset.
The following motor parameters are defined in accordance with the power unit: p0300 ... p0311.
Value: 0: Inactive
1: Start a parameter reset
3: Start download of volatile parameters from RAM
10: Start loading the parameters saved with p0971=10
11: Start loading the parameters saved with p0971=11
12: Start loading the parameters saved with p0971=12
30: Start loading the delivery state saved with p0971=30
100: Start a BICO interconnection reset
300: Only Siemens internal
NOTICE
After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Parameters
7.3 Parameters
SINAMICS G120XA converter
458 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB