p0861 Line contactor monitoring time / LineContact t_mon
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2634
Min:
0 [ms]
Max:
5000 [ms]
Factory setting:
100 [ms]
Description: Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency: See also: p0860, r0863
See also: F07300
Note
The monitoring function is disabled for the factory setting of p0860.
r0863.0...1 CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word and control word of the drive coupling.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Closed-loop control operation Yes No -
01 Energize contactor Yes No 2634
Note
For bit 01:
Bit 1 is used to control an external line contactor.
p0867 Power unit main contactor holding time after OFF1 / PU t_MC after OFF1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.0 [ms]
Max:
500.0 [ms]
Factory setting:
50.0 [ms]
Description: Sets the main contactor holding time after OFF1
Dependency: See also: p0869
Note
After withdrawing the OFF1 enable (source of p0840), the main contactor is opened after the main contactor holding
time has elapsed.
For p0869 = 1 (keep main contactor closed for STO), after withdrawing STO, the switching on inhibited must be
acknowledged via the source of p0840 = 0 (OFF1) and before the main contactor holding time expires, should go back
to 1, otherwise the main contactor will open.
When operating a drive connected to SINUMERIK, which only closes the main contactor with the OFF1 command
(blocksize, chassis), p0867 should be set as a minimum to 50 ms.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 453