r29641 CO: Extented setpoint channel setpoint output / Setp output
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Displays the actual output of the extended setpoint channel setpoint.
p29642 BI: Ramp-function generator, accept setpoint / Total setp sel
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for accepting the setpoint of the ramp-function generator.
p29643 CI: Ramp-function generator setpoint input / Total Setpoint
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for inputting the setpoint of the ramp-function generator.
p29650[0...n] DI selection for ON/OFF2 / DI sel ON/OFF2
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: -
Min:
-1
Max:
5
Factory setting:
0
Description: Defines the DI selection for ON/OFF2. After setting, configuration will be done internally(Except DP/PN variants),
p0840[0...n] = r29659.0
p0844[0...n] = r29659.1
p29652[0...n] = 722.n
You can also configure p29651[0...n] and p29652[0...n] after setting p29650[0...n].
Similar to p0840[0...n] and p0844[0...n], p29651[0...n] and p29652[0...n] are for ON/OFF1 input and OFF2 input
respectively.
Value: -1: NONE
0: DI0
1: DI1
2: DI2
3: DI3
4: DI4
5: DI5
Note
On variants with PN/DP interface , when ON/OFF2 enabled(p29650>=0), the configuration of p840 and p844 will not
be updated internally. ON/OFF2 is only effective if both are configured as r29659 bit0 and bit1 respectively.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 721