Note
0: No alarm present.
r2133[0...63] Fault value for float values / Fault val float
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description: Displays additional information about the fault that occurred for float values.
Dependency: See also: r0945, r0947, r0948, r0949, r2109, r2130, r2136
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2134[0...63] Alarm value for float values / Alarm value float
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8065
Min:
-
Max:
-
Factory setting:
-
Description: Displays additional information about the active alarm for float values.
Dependency: See also: r2110, r2122, r2123, r2124, r2125, r2145, r2146, r3121, r3123
Note
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
r2135.12...15 CO/BO: Status word faults/alarms 2 / ZSW fault/alarm 2
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2548
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the second status word of faults and alarms.
Bit field: Bit Signal name 1 signal 0 signal FP
12 Fault motor overtemperature Yes No 8016
13 Fault power unit thermal overload Yes No 8021
14 Alarm motor overtemperature Yes No 8016
15 Alarm power unit thermal overload Yes No 8021
r2136[0...63] Fault time removed in days / t_flt resolv days
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8060
Min:
-
Max:
-
Factory setting:
-
Description: Displays the system runtime in days when the fault was removed.
Dependency: See also: r0945, r0947, r0948, r0949, r2109, r2130, r2133, p8401
NOTICE
The time comprises r2136 (days) and r2109 (milliseconds).
Parameters
7.3 Parameters
SINAMICS G120XA converter
586 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB