Description: Sets the signal source for the setpoint 1 of the technology controller.
Dependency: See also: p2254, p2255
p2254[0...n] CI: Technology controller setpoint 2 / Tec_ctrl setp 2
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the setpoint 2 of the technology controller.
Dependency: See also: p2253, p2256
p2255 Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling for the setpoint 1 of the technology controller.
Dependency: See also: p2253
p2256 Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling for the setpoint 2 of the technology controller.
Dependency: See also: p2254
p2257 Technology controller ramp-up time / Tec_ctrl t_ramp-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramp-up time of the technology controller.
Dependency: See also: p2258
Note
The ramp-up time is referred to 100 %.
p2258 Technology controller ramp-down time / Tec_ctrl t_ramp-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramp-down time of the technology controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
612 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB