p1750[0...n] Motor model configuration / MotMod config
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 0000 0000 0000 bin
Description: Sets the configuration for the motor model.
Bit 0 = 1: Forces open-loop speed-controlled starting (ASM).
Bit 1 = 1: Forces the system to pass through frequency zero, open-loop-controlled (ASM).
Bit 2 = 1: Drive remains in full closed-loop control mode, even at zero frequency (ASM).
Bit 3 = 1: Motor model evaluates the saturation characteristic (ASM).
Bit 6 = 1: If the motor is blocked, sensorless vector control remains speed-controlled (ASM).
Bit 7 = 1: Use rugged switchover limits to switchover the model (open-loop/closed-loop controlled) for regenerative
operation (ASM).
Bit 8 = 1: Open-loop speed controlled operation independent of the speed setpoint (except for OFF3) (ASM).
Bit field: Bit Signal name 1 signal 0 signal FP
00 Controlled start Yes No -
01 Controlled through 0 Hz Yes No -
02 Closed-loop ctrl oper. down to zero freq. for passive loads Yes No -
03 Motor model Lh_pre = f(PsiEst) Yes No -
06 Closed-loop/open-loop controlled (PMSM) for a blocked
motor
Yes No -
07 Use rugged changeover limits Yes No -
08 Closed-loop controlled until wait time p1758 has expired Yes No -
Dependency: See also: p0500
CAUTION
Do not use bit 6 = 1 if the motor can be slowly reversed by the load at the torque limit. Long delay times due to blocking
(p2177 > p1758) can cause the motor to stall. In this case you should deactivate the function or use closed-loop control
throughout the speed range (note the information re bit 2 = 1).
Parameters
7.3 Parameters
SINAMICS G120XA converter
534 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB